New versions of the GfA TS Control Panels TS 959, TS 970, TS 971 and TS 981 incorporate a neat little feature which means they are all set for use with BS EN12453:2017 safety enabled devices.
Hardware on the TS control panels has been modified slightly, with the interface X2 for door switches changed to resistor evaluation. As shown in the table the previous wired link on the TS control panels has been replaced with a factory installed 5K ohm resistor (right hand image) and the colour of the plugs has been changed from green to black to enable installers to easily distinguish between older and newer versions of the TS door controls.
If the resistor is not present, for example in the case of a short circuit, fault to the door safety edge or open safety circuit due to triggered slack-rope or pass-door switches, operating the door will not be possible. A corresponding fault code will be displayed. (F1.2 / F1.7 / F1.8)
What does BS EN12453:2017 say about monitoring switches?
The modification made to BS EN12453:2017 requires the monitoring of switches used on industrial door safety devices.
The new standard for powered gates, doors and barriers (BS EN12453:2017) although not fully adopted in the UK incorporates an important requirement which is supported by the new TS Control Panel range.
Standard Features of GfA TS Control Panels